Thermocouples for temperature measurement up to 1,700 °C

Thermocouples generate a voltage directly dependent on temperature. They are particularly suited for high temperatures up to 1,700 °C. Instrument designs from mineral-insulated sheathed cable are very resistant against extremely high vibration loads (depending on instrument model, sensor element and wetted materials). For thermocouples, the accuracy classes 1 and 2 apply (standard and special). They are available with a tolerance value in accordance with IEC 60581 / ASTM E230.

Sales contact

WIKA Merna Tehnika d.o.o.

Tel.:
+381 11 2763 722
Fax:
+381 11 2753 674
info.rs@wika.com

FAQ

What is green rot?

Thermocouples are subject to ageing and change their temperature/thermal voltage characteristic.
In Type K thermocouples high temperatures can result in substantial changes to the thermal voltage due to chrome depletion in the NiCr leg, leading to a lower ther ... More

What is the permissible minimum bending radius for an MI cable?

VDI/VDE 3511 Sheet 2 recommends a radius of curvature R of ≥ 5 x D (D=external diameter of the MI cable), some manufacturers of MI cable even give ≥ 3 x D as the minimum bending radius.